VOP Cables

 

Approximately

Approximately

No. cores x

cross-sec

mm²

Outer

diameter

Ø mm

Copperweightkg/km

Cableweight

kg/km

No. cores x

cross-sec

mm²

Outer

diameter

Ø mm

Copperweightkg/km

Cableweight

kg/km

3G0.5

8.4

45.0

111

18G0.5

16.8

170.0

425

4G0.5

9.1

55.0

128

25G0.5

19.5

254.0

560

5G0.5

10.1

67.0

154

27G0.5

19.8

265.0

602

7G0.5

11.5

82.0

204

34G0.5

21.4

298.0

650

10G0.5

13.4

115.0

252

36G0.5

21.6

317.0

690

12G0.5

13.7

140.0

275

41G0.5

23.8

349.0

785

16G0.5

15.9

160.0

352

50G0.5

25.4

470.0

1042

H05VVC4V5-K

<VDE> <HAR> H05VVC4V5-K 7G1mm²

Application

This type is used as measuring and control cable in tool machinery, air-conditioners, conveyor belts and as connecting cables into machines. This cable is manufactured and tested according to DIN VDE 0250 part 405. Totally oil and chemical resistant cable, ideal for use when protection from electromagnetic interferences is required. Recommended for medium mechanical stresses.

Cable structure

Technical data

CoresBare copper, fine stranded wire conductors to DIN VDE 0295 cl.5 and IEC 228 cl.5

Core insulationPVC TI2 Cores stranded in layers

Color codingBlack with white numbering according to DIN VDE 0293 All cables made of 3 cores and above contain green/yellow earthing core in the outer layer

Inner sheathSpecial PVC TM2

ScreeningTinned copper braided, 85% coverage

Outer sheathSpecial PVC TM5, grey color RAL 7001 self-extinguishing and flame retardant according toDIN VDE 0472 part 804 and IEC 60332-1

SpecificationsControl cables made of special PVC, according toDIN VDE 0250 part 405 to HD 21.13S1

Temperature rangeFlexing from -5°C up to +70°CFixed installation from -40°C up to +70°C

Nominal voltageUo/U 300/500 V

Insulation resistance20 MΩ/km minimum

Minimum bending radius10 x cable Ø minimum

| flexible cable, number coded, CU-screened| and with VDE approval (NYSLYCYÖ –JZ)

www.vopcables.com

Control Cables

 

Approximately

Approximately

No. cores x

cross-sec

mm²

Outer

diameter

Ø mm

Copperweightkg/km

Cableweight

kg/km

No. cores x

cross-sec

mm²

Outer

diameter

Ø mm

Copperweightkg/km

Cableweight

kg/km

61G0.5

27.2

530.0

1150

50G1

29.5

692.0

1390

65G0.5

28.9

563.0

1200

61G1

31.2

883.0

1520

65G1

32.4

914.0

1618

3G0.75

8.8

52.0

128

4G0.75

9.9

65.0

153

3G1.5

10.2

76.0

190

5G0.75

10.8

74.0

180

4G1.5

10.8

95.0

220

7G0.75

12.1

105.0

245

5G1.5

11.6

111.0

259

10G0.75

14.1

150.0

320

7G1.5

13.5

150.0

356

12G0.75

14.5

180.0

350

10G1.5

15.8

230.0

458

16G0.75

15.8

228.0

405

12G1.5

17.1

266.0

560

18G0.75

17.5

252.0

490

16G1.5

18.7

348.0

598

25G0.75

21.0

312.0

660

18G1.5

20.0

379.0

760

27G0.75

21.4

331.0

710

20G1.5

21.1

399.0

795

34G0.75

22.5

399.0

845

25G1.5

24.2

505.0

1035

36G0.75

22.6

410.0

920

27G1.5

24.6

555.0

1086

41G0.75

24.0

420.0

1028

34G1.5

26.9

754.0

1350

50G0.75

26.0

576.0

1180

40G1.5

28.3

790.0

1398

61G0.75

29.9

678.0

1435

44G1.5

29.8

828.0

1462

65G0.75

31.7

708.0

1520

50G1.5

32.7

1032.0

1786

61G1.5

37.5

1238.0

1994

3G1

9.4

59.0

144

65G1.5

38.0

1296.0

2210

4G1

10.3

73.0

178

5G1

11.0

85.0

210

3G2.5

11.9

115.0

243

7G1

12.9

112.0

272

4G2.5

12.8

163.0

298

10G1

14.9

164.0

375

5G2.5

13.9

200.0

365

12G1

16.4

185.0

428

7G2.5

15.9

255.0

480

16G1

17.8

235.0

520

12G2.5

20.6

468.0

760

18G1

19.1

258.0

599

18G2.5

24.9

620.0

1052

20G1

20.0

300.0

640

25G2.5

29.0

897.0

1450

25G1

22.5

365.0

790

30G2.5

30.6

1030.0

1685

27G1

22.8

375.0

835

34G2.5

33.0

1050.0

1892

34G1

25.2

460.0

1050

40G2.5

36.0

1325.0

2270

40G1

27.0

586.0

1125

34G2.5

33.0

1050.0

1892

44G1

28.1

625.0

1198

40G2.5

36.0

1325.0

2270

H05VVC4V5-K | flexible cable, number coded, CU-screened and with VDE approval (NYSLYCYÖ –JZ)

For cross sections, that are not mentioned on the adove board, please contact our company.

www.vopcables.com

Control Cables

Contact