PT1 (or PT2), TY2, COL, SCR, SWA, PVC
Cable structure
Technical data
CoresPlain annealed flexible copper conductors
Core insulationPE (PT1, TY2)PVC (PT2, TY)
Core codingColored cores (See pg. 196 BOARD 1 for PE and pg. 197 BOARD 2 for PVC) Cores are laid up to pairs
ScreeningAluminium tape with drain wire 0.5mm²
Inner insulationPolyethylene
ArmoringGalvanised steel wire screening
Outer sheathPVC, black or blue color
Temperature rangeFrom -20ºC up to +65ºC
Bending radius6 x Ø cableShould not be installed at temperatures below 0ºC
Application
This type is used as instrumentation, control and communication cable in both outdoor and indoor fixed installations. It is resistant to tensile stress and suitable for direct burial underground. Recommended when antirodent protection is required.
Approximately
Approximately
No. cores x
cross-sec
mm²
Outer
Diameter
Ø mm
Copper
Weight
kg/km
Cable
Weight
kg/km
No. cores x
cross-sec
mm²
Outer
Diameter
Ø mm
Copper
Weight
kg/km
Cable
Weight
kg/km
2x2x0.5
11.7
300
20/16
1x2x1.5
12.3
330
20/16
5x2x0.5
17.3
560
20
2x2x1.5
13.7
420
20S
10x2x0.5
22.3
970
25
5x2x1.5
21.5
940
25
20x2x0.5
28.5
1640
32
10x2x1.5
27.8
1050
32
30x2x0.5
33.3
2110
40
20x2x1.5
35.1
2400
40
50x2x0.5
41.5
3270
50S
30x2x1.5
41.9
3120
50S
1x3x0.5
11
276
20/16
50x2x1.5
53.4
5310
63S
1x3x1.5
12.6
376
20/16
2x2x0.75
12.3
330
20/16
5x2x0.75
19.2
750
20
1x2x2.5
13.1
395
20S
10x2x0.75
24.7
1260
25
2x2x2.5
15.9
490
20
20x2x0.75
30.7
1890
32
5x2x2.5
26.5
1430
20
30x2x0.75
36.9
2440
40
10x2x2.5
35.1
2235
40
50x2x0.75
46.4
3890
50
20x2x2.5
46.7
3935
50
1x3x0.75
11.4
307
20/16
1x3x2.5
13.7
407
20S
| instrumentation cable galvanised steel wire armoured BS 5308