Application
This cable is used on indoor installations, wherever high security specifications are required for the protection from fire of human life and materials. In case of fire, circuit integrity of the system where this type is used can be maintained for 30 minutes, while it appears low smoke emissions and zero halogen. Not recommended for direct burial under-ground or underwater without conduits or tubes.

Cable structure
Technical data
CoresSolid or stranded bare copper wires according to DIN VDE 0295 cl.1 and IEC 60228 cl.1 and cl.2
Core insulation1st insulationHigh quality flame resistant, ceramic compound2nd insulationCross-linked polymer compoundHxI1 according to DIN VDE 0266
Color codingAccording to DIN VDE 0293, from 3cores and above contains green/yellow earthing core
WrappingHalogen free compound
Outer sheathPolyolefin compound HM4, according to DIN VDE 0276-604,CENELEC HD 604 S1, in orange color
re = round conductor, single wire
rm = round conductor, multiple-wire
SpecificationsDIN VDE 0276-604
Temperature rangeDuring installation: from -5°C up to +50°C
Fixed installation: from -5°C up to +90°C
Nominal voltageUo/U 0.6/1 kV
Minimum bending radiusSingle core: 12 x cable Ø
Multi core: 15 x cable Ø
Halogen freeDIN VDE 0482-267, EN 50267 and IEC 60754-2
Flame retardantDIN VDE 0482-265, EN 50265 and IEC 60332-1
Reduced flame propagationDIN VDE 0472-804/C, CENELEC HD 405.3 and IEC60332-3 cat C and cat A
Low smoke emissionDIN VDE 0482-268, EN 50268 and IEC 61034-1Insulation integrity FE180
DIN VDE 0472-814, IEC 60331, NBN C30-004 cat F3
FuncionalityH30: DIN41012-12
NHXHFE180/E30
Approximately
Approximately
No. cores x
cross-sec
mm²
Outer
Diameter
Ø mm
Copper
Weight
kg/km
Cable
Weight
kg/km
No. cores x
cross-sec
mm²
Outer
Diameter
Ø mm
Copper
Weight
kg/km
Cable
Weight
kg/km
1×4 re
8.0
38.0
104
1×95 rm
19.0
912.0
1103
1×6 re
8.0
58.0
129
1×120 rm
20.0
1152.0
1332
1×10 re
9.0
96.0
176
1×150 rm
22.0
1440.0
1664
1×16 rm
11.0
154.0
252
1×185 rm
24.0
1776.0
2048
1×25 rm
12.0
240.0
358
1×240 rm
28.0
2304.0
2680
1×35 rm
13.0
336.0
460
1×300 rm
31.0
2880.0
3200
1×50 rm
15.0
480.0
601
1×70 rm
17.0
672.0
824
2×1.5 re
12.0
29.0
224
NHXH FE180/E30 0.6/1KV
| fire resistant power cables for 30 minutes | circuit integrity
Fire Resistant Cables
www.vopcables.com

NHXH FE180/E30 fire resistant power cables for 30 minutes circuit integrity
Approximately
Approximately
No. cores x
cross-sec
mm²
Outer
Diameter
Ø mm
Copper
Weight
kg/km
Cable
Weight
kg/km
No. cores x
cross-sec
mm²
Outer
Diameter
Ø mm
Copper
Weight
kg/km
Cable
Weight
kg/km
2×2.5 re
13.0
48.0
266
4×25 rm
27.0
960.0
1636
2×4 re
14.0
77.0
326
4×35 rm
30.0
1344.0
2126
2×6 re
15.0
115.0
395
4×50 rm
33.0
1920.0
2791
2×10 re
17.0
192.0
525
4×70 rm
38.0
2688.0
3842
2×16 rm
20.0
307.0
756
4×95 rm
44.0
3648.0
5120
2×25 rm
23.0
480.0
1059
4×120 rm
47.0
4608.0
6180
2×35 rm
24.0
672.0
1120
4×150 rm
52.0
5760.0
7727
3×1.5 re
13.0
43.0
252
5×1.5 re
15.0
72.0
351
3×2.5 re
14.0
72.0
305
5×2.5 re
16.0
120.0
428
3×4 re
15.0
115.0
380
5×4 re
18.0
192.0
545
3×6 re
16.0
173.0
468
5×6 re
19.0
288.0
685
3×10 re
18.0
288.0
635
5×10 re
21.0
480.0
942
3×16 rm
21.0
461.0
921
5×16 rm
25.0
768.0
1388
3×25 rm
24.0
720.0
1308
5×25 rm
30.0
1200.0
2005
3×35 rm
27.0
1080.0
1673
5×35 rm
33.0
1680.0
2602
3×50 rm
30.0
1440.0
2200
5×50 rm
37.0
2400.0
3418
3×70 rm
34.0
2016.0
3017
3×25+16 rm
26.0
874.0
1505
7×1.5 re
17.0
101.0
427
3×35+16 rm
28.0
1162.0
1852
7×2.5 re
18.0
168.0
533
3×50+25 rm
32.0
1680.0
2492
3×70+35 rm
36.0
2352.0
3382
12×1.5 re
21.0
173.0
659
3×95+50 rm
42.0
3216.0
4570
12×2.5 re
23.0
288.0
832
3×120+70 rm
45.0
4128.0
5551
3×150+70 rm
49.0
4992.0
6704
19×1.5 re
25.0
274.0
922
3×185+95 rm
55.0
6240.0
8343
19×2.5 re
27.0
456.0
1186
4×1.5 re
14.0
58.0
295
24×1.5 re
29.0
346.0
1152
4×2.5 re
15.0
96.0
381
24×2.5 re
31.0
576.0
1500
4×4 re
16.0
154.0
459
4×6 re
18.0
230.0
571
30×1.5 re
31.0
432.0
1383
4×10 re
19.0
384.0
781
30×2.5 re
34.0
720.0
1804
4×16 rm
23.0
614.0
1147
www.vopcables.com
Fire Resistant Cables