Application
2YSLC11Y-J is a power cable used for engine feeding on indoor industrial installations. It is ideal for high noise environment and areas with frequency transformers and electromagnetic interferences.
Cable structure
Technical data
CoresStranded bare copper conductors according toDIN IEC 60228 cl.5
Core insulationPolyethylene of medium density
Core codingBlack, blue, brown, green/yellow
WrappingPolyester transparent foil1st Screening: plastic aluminium foil2nd Screening: tinned copper, 85% coverage
Screen wrappingPolyester tape
Outer sheathPolyurethane, orange color RAL 2003Flame retardant according to IEC 60332-1, EN 50265-2-1
Nominal voltageUo/U 0.6/1 kV
Temperature rangeFlexing from -30ºC up to +80ºC Fixed istallation from -40ºC up to +80ºC
Insulation resistance> 200 GΩ/km
Minimum bending radiusFlexing from 15 x Ø cable Fixed installation 8 x Ø cable
Oil resistanceHD 505.2.1, VDE 0472
Hydrolisis resistanceHD 22.10
Ozone resistanceHD 22.2
| servo cable, double screened with| PVC outer sheath
2YSLC11Y-J
Cores x cross-secin mm²
Approximately
Outer Diameter
Ø mm
Copper Weight
kg/km
Cable Weight
kg/km
Outer Sheath Resistance 20ºC (Ω/km)
4×1.5
10.3
95
196
13.3
4×2.5
12.2
150
275
7.98
4×4
14
238
350
4.95
4×6
15.7
334
480
3.3
4×10
19.9
533
807
1.91
4×16
23
789
1064
1.21
4×25
27
1236
1667
0.78
4×35
30
1662
2282
0.554
4×50
36.1
2345
2903
0.386
For cross sections that are not mentioned on the table above, please contact our sales department.