VOP Cables

Vop_Catalogue_2020_WEB_USE_ONLY_ENG-177

Cores x cross-secin mm²

Approximately

Outer Diameter

Ø mm

Copper Weight

kg/km

Cable Weight

kg/km

Outer Sheath Resistance 20ºC (Ω/km)

4×1.5

10.6

95

214

13.3

4×2.5

12.3

150

291

7.98

4×4

14.5

238

390

4.95

4×6

16.4

334

529

3.3

4×10

20.1

533

852

1.91

4×16

23.4

789

1164

1.21

4×25

27

1236

1707

0.78

4×35

30.7

1662

2591

0.554

4×50

36.1

2345

3186

0.386

Application

2YSLCY-J is used as power cable for engine feeding. Suitable for indoor industrial installations. Idea for high noise environment and areas with frequency transformers and electromagnetic intereferences.

2YSLCY-J

Cable structure

Technical data

CoresBare copper conductors according to IEC 60228 cl.5

Core InsulationPolyethylene medium density

Core codingBlack, blue, brown, green/yellow

Overal core wrappingPolyester transparent foil1st screening: Aluminium foil2nd screening: Tinned copper, braid coverage 85%

Outer sheathTransparent PVC type TM2Flame Retardant acc. to IEC 60332-1, EN 50265-2-1 or black RAL 9005, oil resistant according to IEC 60811-2-1

Nominal voltageUo/U 0.6/1 kV

Temperature rangeFlexing from -5ºC up to +80ºCFixed istallation from -40ºC up to +80ºC

Insulation resistance> 1 x km

Minimum bending radiusFlexing 15 x Ø cableFixed installation 8 x Ø cable

| servo double screened cables with| transparent outer sheath of PVC

For cross sections that are not mentioned on the table above, please contact our sales department.

www.vopcables.com

Servo, Motor and Inverter Cables

Contact

    This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.