VOP Cables

Vop_Catalogue_2020_WEB_USE_ONLY_ENG-177

Cores x cross-secin mm²

Approximately

Outer Diameter

Ø mm

Copper Weight

kg/km

Cable Weight

kg/km

Outer Sheath Resistance 20ºC (Ω/km)

4×1.5

10.6

95

214

13.3

4×2.5

12.3

150

291

7.98

4×4

14.5

238

390

4.95

4×6

16.4

334

529

3.3

4×10

20.1

533

852

1.91

4×16

23.4

789

1164

1.21

4×25

27

1236

1707

0.78

4×35

30.7

1662

2591

0.554

4×50

36.1

2345

3186

0.386

Application

2YSLCY-J is used as power cable for engine feeding. Suitable for indoor industrial installations. Idea for high noise environment and areas with frequency transformers and electromagnetic intereferences.

2YSLCY-J

Cable structure

Technical data

CoresBare copper conductors according to IEC 60228 cl.5

Core InsulationPolyethylene medium density

Core codingBlack, blue, brown, green/yellow

Overal core wrappingPolyester transparent foil1st screening: Aluminium foil2nd screening: Tinned copper, braid coverage 85%

Outer sheathTransparent PVC type TM2Flame Retardant acc. to IEC 60332-1, EN 50265-2-1 or black RAL 9005, oil resistant according to IEC 60811-2-1

Nominal voltageUo/U 0.6/1 kV

Temperature rangeFlexing from -5ºC up to +80ºCFixed istallation from -40ºC up to +80ºC

Insulation resistance> 1 x km

Minimum bending radiusFlexing 15 x Ø cableFixed installation 8 x Ø cable

| servo double screened cables with| transparent outer sheath of PVC

For cross sections that are not mentioned on the table above, please contact our sales department.

www.vopcables.com

Servo, Motor and Inverter Cables