Cores x cross-secin mm²
Approximately
Outer Diameter
Ø mm
Copper Weight
kg/km
Cable Weight
kg/km
Outer Sheath Resistance 20ºC (Ω/km)
4×1.5
10.6
95
214
13.3
4×2.5
12.3
150
291
7.98
4×4
14.5
238
390
4.95
4×6
16.4
334
529
3.3
4×10
20.1
533
852
1.91
4×16
23.4
789
1164
1.21
4×25
27
1236
1707
0.78
4×35
30.7
1662
2591
0.554
4×50
36.1
2345
3186
0.386
4×70
42.3
3196
3554
0.272
4×95
47.7
4316
4680
0.206
4×120
51.9
5435
5859
0.161
4×150
57.5
6394
7294
0.129
4×185
61.1
7639
8954
0.106
Application
This type is used as power cable for engine feeding. Suitable for indoor industrial installations. Ideal for high noise environment and areas with frequency transformers and electromagnetic interferences.
2YSLCYK-J
Cable structure
Technical data
CoresBare copper conductors according to IEC 60228 cl. 5
Copper InsulationPolyethylene medium density
Core codingBlack, blue, brown, yellow/green
Core wrappingPolyester transparent foil 1st screening: aluminium foil2nd screening: tinned copper, coverage 85%
Screen wrappingPolyester tape
Outer sheathPolyurethane, orange color RAL 2003Flame Retardant according to IEC 60332-1, EN 50265-2-1
Nominal voltageUo/U 0.6/1 kV
Temperature rangeFlexing from -5ºC up to +70ºC Fixed installation from -40ºC up to +70ºC
Insulation resistance> 200 ΜΩ/km
Minimum bending radiusFlexing 15 x Ø cableFixed installation 8 x Ø cable
| Servo cable, double screened, polyurethane | outer sheath
For cross sections that are not mentioned on the table above, please contact our sales department.
2YSLCYK – J 4G4 mm2
www.vopcables.com
Servo, Motor and Inverter Cables