Application

This type is used as power cable both on indoor and outdoor fixed installations. Suitable for direct burial under-ground. Resistant to tensile strength. Antirodent production is also offered on this type. In case of fire it appears low smoke emissions and zero halogen.

CU/XLPE/CTS/LSZH/AWA/LSZH

Cable structure

Technical data

CoresPlain annealed flexible copper conductors

Core insulationXLPE, brown color and a copper tape

Overal insulationLSZH (Low Smoke Zero Halogen) black color

ArmoringAluminium wires

Outer sheathLSZH (Low Smoke Zero Halogen), red color

Nominal voltage11 kV

Temperature rangeup to +90ºC

Bending radius15 x Ø cable

Should not be installed at temperatures below 0ºC

Cores x cross-secin mm²

Approximately

Outer Diameter

Cable Weight

kg/km

Gland size

σε mm

1×50

28.8

1200

32

1×70

29.9

1500

32

1×95

31.7

1600

32

1×120

33.3

2100

40

1×150

35.7

2500

40

1×185

37.5

2900

40

1×240

40.1

3600

50S

1×300

42.4

4300

50S

1×400

45.8

5200

50S

1×500

50.5

6500

50

1×630

54.7

8000

63S

| medium voltage power cable 6.3/11 kV