VOP Cables

Vop_Catalogue_2020_WEB_USE_ONLY_ENG-161

Application

This type is used as power cable both on indoor and outdoor fixed installations. Suitable for direct burial underground. Resistant to tensile strength. Antirodent production is also offered on this type. In case of fire it appears low smoke emissions and zero halogen.

CU/XLPE/CTS/LSZH/SWA/LSZH

Cable structure

Technical data

CoresPlain annealed flexible copper conductors

Core insulationXLPE and copper tape

Core codingColored cores brown, black, grey

Overal insulationLSZH (Low Smoke Zero Halogen), black color

ArmoringGalvanized steel wires

Outer sheathLSZH (Low Smoke Zero Halogen), red color

Nominal voltage11 kV

Temperature rangeUp to +90ºC

Bending radius-12 x Ø cable

Should not be installed at temperatures below 0ºC

| medium voltage power cable 6.3/11 kV

| galvanized steel wire armored BS 7835

Cores x cross-secin mm²

Approximately

Outer Diameter

Cable Weight

kg/km

Gland size

in mm

3×35

51.6

4900

50

3×50

54.6

5600

63S

3×70

58.5

6500

63S

3×95

62.6

7800

63

3×120

66.6

8900

75S

3×150

68.8

10000

75

3×185

74.1

11600

75

3×240

81.2

14800

90

3×300

86.8

17300

90