Application
This type is used as power cable both on indoor and outdoor fixed installations. Suitable for direct burial underground. Resistant to tensile strength. Antirodent production is also offered on this type. In case of fire it appears low smoke emissions and zero halogen.
CU/XLPE/CTS/LSZH/SWA/LSZH
Cable structure
Technical data
CoresPlain annealed flexible copper conductors
Core insulationXLPE and copper tape
Core codingColored cores brown, black, grey
Overal insulationLSZH (Low Smoke Zero Halogen), black color
ArmoringGalvanized steel wires
Outer sheathLSZH (Low Smoke Zero Halogen), red color
Nominal voltage11 kV
Temperature rangeUp to +90ºC
Bending radius-12 x Ø cable
Should not be installed at temperatures below 0ºC
| medium voltage power cable 6.3/11 kV
| galvanized steel wire armored BS 7835
Cores x cross-secin mm²
Approximately
Outer Diameter
Cable Weight
kg/km
Gland size
in mm
3×35
51.6
4900
50
3×50
54.6
5600
63S
3×70
58.5
6500
63S
3×95
62.6
7800
63
3×120
66.6
8900
75S
3×150
68.8
10000
75
3×185
74.1
11600
75
3×240
81.2
14800
90
3×300
86.8
17300
90
www.vopcables.com
Medium Voltage Cables