Application
This type is used as power cable both on indoor and outdoor fixed installations. Suitable for direct burial under-ground. Resistant to tensile strength. Antirodent production is also offered on this type. In case of fire it appears low smoke emissions and zero halogen.
CU/XLPE/CTS/PVC/SWA/PVC
Cable structure
Technical data
CoresPlain annealed flexible copper conductors
Core insulationXLPE and copper tape
Core codingColored cores: brown, black, grey
Overal insulationPVC, black color
ArmoringGalvanized steel wires
Outer sheathPVC, red color
Nominal voltage11 kV
Temperature rangeup to +90ºC
Bending radius12 x Ø cable
Should not be installed at temperatures below 0ºC
| medium voltage power cable 6.3/11 kV| galvanized steel wire armored BS 6622
Cores x cross-secin mm²
Approximately
Outer Diameter
Cable Weight
kg/km
Gland size
σε mm
3×25
48.8
4400
50
3×35
51.6
4900
50
3×50
54.6
5600
63S
3×70
58.5
6500
63S
3×95
62.6
7800
63
3×120
66.6
8900
75S
3×150
68.8
10000
75S
3×185
74.1
11600
75
3×240
81.2
14800
90
3×300
86.8
17300
90
3×400
93
19300
–
www.vopcables.com