VOP Cables

Vop_Catalogue_2020_WEB_USE_ONLY_ENG-139

Application

FG16R16 power cable type is used on both indoor and outdoor installations. Suitable also for in-wall, cable trays and underground installations.

Cable structure

Technical data

CoresStranded of flexible copper wires according to DIN VDE 0295

InsulationEthylopropylene rupper, type G7

Outer sheathThermoplastic PVC type RzFlame retardant according to CEI 20-22/ 1-5, grey color

Nominal voltageUo/U 0.6/1 kV

Temperature rangeFrom -15ºC up to 90ºC

Minimum bending radius4 x cable Ø

| flexible power cables, single core 0,6/1 kV

FG16R16 1×25 mm²

FG16R16

Cores x cross-secin mm²

Approximately

Outer Diameter

Ø mm

Copper Weight kg/km

Cable Weight

kg/km

Max Resistanceat 20oC

1×1.5

7.00

14.40

51.00

13.30

1×2.5

7.40

24.00

65.00

7.98

1×4

8.20

38.00

80.00

4.95

1×6

8.90

58.00

105.00

3.30

1×10

9.80

96.00

150.00

1.91

1×16

10.90

154.00

200.00

1.21

1×25

13.00

240.00

300.00

0.780

1×35

14.00

336.00

390.00

0.554

1×50

15.70

480.00

540.00

0.386

1×70

18.00

672.00

740.00

0.272

1×95

20.40

912.00

940.00

0.206

1×120

22.30

1152.00

1200.00

0.161

1×150

24.50

1440.00

1480.00

0.129

1×185

27.40

1776.00

1830.00

0.106

1×240

30.50

2304.00

2340.00

0.0801

1×300

34.00

2900.00

2950.00

0.0641

1×400

37.70

3870.00

3835.00

0.0486

www.vopcables.com