H05V-K & H07V-K
Application
They are cables for general use, for permanent installation, for switch doards, in grounding and in domestic
machines.
Cable structure
Technical data
CoresΒare copper fine wire stranded according toDIN VDE 0295 cl.5 and IEC 60228 cl5
Core insulationΤhermoplastic PVC, compound TI 1
Maximum tensile stresses50 N/mm² from the copper element
SpecificationsDIN VDE 0281 and HD 21
Temperature rangeFlexing from –5°C up to +70°CFixed installation from -30°C up to +80°C
Nominal voltageH05V-K Uo/U 300/500 V for cross sections up to 1mm2H07V-K Uo/U 450/750 V for cross sections 1.5mm2 and over
Minimum bending radiusH05V-K 4 x cable ØH07V-K 6 x cable Ø
Cores x cross-sec in mm²
Approximately
Type
Outer Diameter
Ø mm
Outer Diameter
Ø mm
Cable Weight
kg/km
Minimum mm
Maximum mm
H05V -K
0.5
1.0
2.1
4.8
8
0.75
1.2
2.2
7.2
11
1
1.5
2.4
9.6
13
H07V-K
1.5
2.8
3.4
14.4
21
2.5
3.4
4.1
24.0
32
4
3.9
4.8
38.0
17
6
4.4
5.3
58.0
65
10
5.7
6.8
96.0
110
16
6.7
8.7
154.0
170
25
8.4
10.2
240.0
255
35
9.7
11.7
336.0
345
50
11.5
13.9
480.0
495
70
13.2
16.0
672.0
680
95
15.1
18.2
912.0
900
120
16.7
20.2
1152.0
1135
150
18.6
22.5
1440.0
1410
185
20.6
24.9
1776.0
1920
240
23.5
28.4
2304.0
2260
Continuous stock in all cross sections in the following colors:
Black, blue, brown, red, white, grey, pink, orange, green/yellow, violet.
| flexible PVC cables (NYAF)
www.vopcables.com
Control Cables