VOP Cables

 

H05V-K & H07V-K

Application

They are cables for general use, for permanent installation, for switch doards, in grounding and in domestic

machines.

Cable structure

Technical data

CoresΒare copper fine wire stranded according toDIN VDE 0295 cl.5 and IEC 60228 cl5

Core insulationΤhermoplastic PVC, compound TI 1

Maximum tensile stresses50 N/mm² from the copper element

SpecificationsDIN VDE 0281 and HD 21

Temperature rangeFlexing from –5°C up to +70°CFixed installation from -30°C up to +80°C

Nominal voltageH05V-K Uo/U 300/500 V for cross sections up to 1mm2H07V-K Uo/U 450/750 V for cross sections 1.5mm2 and over

Minimum bending radiusH05V-K 4 x cable ØH07V-K 6 x cable Ø

Cores x cross-sec in mm²

Approximately

Type

Outer Diameter

Ø mm

Outer Diameter

Ø mm

Cable Weight

kg/km

Minimum mm

Maximum mm

H05V -K

0.5

1.0

2.1

4.8

8

0.75

1.2

2.2

7.2

11

1

1.5

2.4

9.6

13

H07V-K

1.5

2.8

3.4

14.4

21

2.5

3.4

4.1

24.0

32

4

3.9

4.8

38.0

17

6

4.4

5.3

58.0

65

10

5.7

6.8

96.0

110

16

6.7

8.7

154.0

170

25

8.4

10.2

240.0

255

35

9.7

11.7

336.0

345

50

11.5

13.9

480.0

495

70

13.2

16.0

672.0

680

95

15.1

18.2

912.0

900

120

16.7

20.2

1152.0

1135

150

18.6

22.5

1440.0

1410

185

20.6

24.9

1776.0

1920

240

23.5

28.4

2304.0

2260

Continuous stock in all cross sections in the following colors:

Black, blue, brown, red, white, grey, pink, orange, green/yellow, violet.

| flexible PVC cables (NYAF)

www.vopcables.com

Control Cables

Contact

    This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.