VOP Cables

 

Approximately

Approximately

No. cores x

cross-sec

mm²

Outer

diameter

Ø mm

Copperweightkg/km

Cableweight

kg/km

No. cores x

cross-sec

mm²

Outer

diameter

Ø mm

Copperweightkg/km

Cableweight

kg/km

12×0.75

4.2 x 33.9

87.0

268

4×4

6.9 x 22.0

154.0

300

18×0.75

4.2 x 50.2

132.0

390

5×4

6.9 x 31.0

288.0

410

24×0.75

4.2 x 66.2

178.0

507

4×6

7.4 x 22.0

230.0

400

12×1

4.4 x 36.2

115.3

300

5×6

7.4 x 31.0

288.0

529

18×1

4.4 x 54.1

206.0

458

24×1

4.4 x 70.9

231.0

592

4×10

9.3 x 27.6

614.0

1010

5×10

11.0 x 43.5

480.0

1125

4×1.5

5.1 x 14.5

58.0

134

8×1.5

5.1 x 25.5

115.0

267

4×16

11.1 x 34.4

614.0

1020

12×1.5

5.1 x 41.8

173.0

425

24×1.5

5.1 x 83.2

348.0

835

4×25

13.7 x 42.6

960.0

1358

4×2.5

5.9 x 17.5

96.0

200

4×35

15.4 x 47.6

1344.0

2125

8×2.5

5.9 x 33.1

192.0

380

12×2.5

5.9 x 49.1

288.0

578

4×50

18.2 x 57

1920.0

2937

24×2.5

5.9 x 102.0

480.0

1150

4×70

20.0 x 64.2

2688.0

4085

H05VVH6-F &

H07VVH6-F

<HAR> H07VVH6-F 8×1.5 mm²

Application

These cable types are mainly used for crane installations, conveyor systems and elevators. Recommended for installations where small bending radius is necessary.

Cable structure

Technical data

CoresBare copper stranded according toDIN VDE 0295 cl.5 and IEC 60228 cl.5

Core insulationSpecial PVCCores laying parallel

Color codingAccording to DIN VDE 0293 up to 5 coresFor 7 or more cores: black white numberingIt is contained green/yellow earthing core

Outer sheathSpecial PVC, black colorSelf-extinguishing according toDIN VDE 0482 IEC 60332.1

SpecificationsDIN VDE 0281

Temperature rangeFlexing from -5°C up to +70°CFixed installation from -40°C up to +80°C

Nominal voltageH05VVH6-F Uo/U 300/500V for cross sectionsup to 1mm2H07VVH6-F Uo/U 450/750V for cross sections 1.5mm2 and over

Minimum bending radius10 x minimum cable Ø

| flat cable for | crane installations

www.vopcables.com

Control Cables

Contact