Application
This cable type is used on indoor fixed installations. Suitable for telephone connections, extensions, security and fire warning systems, wherever high security specifications are required for the protection of human life from fire. The static screen contained in this cable offers signal protection from outer electrical interferences. When burnt, circuit integrity is maintained for 90 minutes, appearing low smoke and zero halogen emissions.
JE-H(st)H Bd
FE180/E90
Cable structure
Technical data
CoresSolid bare copper, with diameter 0.8mm
Core insulationMICA tape and polymer cross – linked comound HI 1 according to DIN VDE 0207-23
Color codingCores are marked with black rings and the units with numbered tape according to, DIN VDE 0815Cores are twisted in pairs, four pairs twisted in a quad, and quads are stranded to unitsUnits are stranded together
Wrapping
1st wrappingPlastic tape
2nd wrappingFiber-glass tape
Drain wireTinned copper
ScreeningAluminium tape
Outer sheathPolyolefin compound HM2 according to DIN VDE 0207-24, in orange color
SpecificationsDIN VDE 0815
Temperature rangeFrom -5ºC up to +70ºC
Nominal voltage(maximum) 225 V
Halogen freeDIN VDE 0482-267, EN 50267 and IEC 60754-2
Flame retardantDIN VDE 0482-265, EN 50265 and IEC 60332-1
Reduced flame propagationDIN VDE 0472-804/C, CENELEC HD 405.3 andIEC 60332-3 cat C and cat A
Low smoke emmisionDIN VDE 0482-268, EN 50268 and IEC 61034-1
Insulation integrity FE180DIN VDE 0472-814, IEC 60331, EN50200,NBN C30-004 cat F3
Funcionality E30DIN 41012-12
| fire resistant and halogen free cables
Approximately
Approximately
No. cores x
cross-sec
mm²
Outer
Diameter
Ø mm
Copper
Weight
kg/km
Cable
Weight
kg/km
No. cores x
cross-sec
mm²
Outer
Diameter
Ø mm
Copper
Weight
kg/km
Cable
Weight
kg/km
2x2x0.8
8.0
25.0
73
20x2x0.8
23.0
206.0
519
4x2x0.8
11.0
45.0
126
32x2x0.8
28.0
326.0
786
8x2x0.8
17.0
85.0
293
40x2x0.8
32.0
407.0
985
12x2x0.8
19.0
126.0
373
52x2x0.8
35.0
529.0
1201
16x2x0.8
21.0
166.0
461
www.vopcables.com