VOP Cables

Vop_Catalogue_2020_WEB_USE_ONLY_ENG-137

Application

N2XCH cables are used on indoor installations where special safety specifications are required for the human life protection in case of fire. Mostly used into hospitals, underground stations, public places with big people concentration etc. Ideal for fixed installations in damp environment and beneath plaster as well as in masonary walls in concrete.

Cable structure

Technical data

CoresSolid or stranded bare copper wires according to DIN VDE 0295 cl.1 or cl.2

Core insulationCross-linked polyethylene 2XI1 according to DIN VDE 0276-604

Color codingΑccording to DIN VDE 0293

WrappingHalogen free compound

ScreeningConcentric conductor of plain copper wires wrapped with copper tape

Outer sheathThermoplastic polyolefin compound HM4 according to DIN VDE 0276-204, in black color

SpecificationsDIN VDE 0276 part 604 CENELEC HD604 S1

Temperature rangeFlexing from -5ºC up to +50ºCFixed installation from -30ºC up to +90ºC

Nominal voltageUo/U 0.6/ 1kV

Minimum bending radiusSingle core 15 x cable ØMulticore 12 x cable Ø

re = round conductor, single wire

rm = round conductor, multi core

| power cables, 0.6/1 kV, with concectric conductor| halogen free

Approximately

Approximately

No. cores x

cross-sec

mm²

Outer

Diameter

Ø mm

Copper

Weight

kg/km

Cable

Weight

kg/km

No. cores x

cross-sec

mm²

Outer

Diameter

Ø mm

Copper

Weight

kg/km

Cable

Weight

kg/km

2×1.5/1.5re

11.0

52.0

162

3×25/16rm

25.0

1003.0

1325

2×2.5/2.5re

12.0

80.0

206

3×35/16rm

27.0

1402.0

1676

2×4/4re

13.0

122.0

300

3×50/25rm

30.0

1723.0

2220

2×6/6re

14.0

183.0

398

3×70/35rm

33.6

2794.0

3051

2×10/16re

17.0

311.0

557

3×95/50rm

36.2

3790.0

4186

2×16/16re

18.9

490.0

778

3×120/70rm

40.1

4785.0

5150

3×150/70rm

42.5

5100.0

5602

3×1.5/1.5re

11.0

66.0

179

3×185/95rm

45.7

6381.0

7100

3×2.5/2.5re

12.0

104.0

233

3×240/120rm

52.8

8240.0

9202

3×4/4 re

14.0

161.0

318

3×6/6 re

15.0

240.0

412

4×1.5/1.5re

12.0

81.0

205

3×10/10re

17.0

408.0

611

4×2.5/2.5re

13.0w

128.0

267

3×16/16re

21.0

643.0

963

4×4/4re

15.0

200.0

377

N2XCH 2X1.5/1.5 Re

N2XCH

www.vopcables.com

Power Cables

Vop_Catalogue_2020_WEB_USE_ONLY_ENG-138

N2XCH καλώδια ισχύος 0.6/1 kV με ομοκεντρικό αγωγό γείωσης, βραδύκαυστα και ελεύθερα αλογόνων

Approximately

Approximately

No. cores x

cross-sec

mm²

Outer

Diameter

Ø mm

Copper

Weight

kg/km

Cable

Weight

kg/km

No. cores x

cross-sec

mm²

Outer

Diameter

Ø mm

Copper

Weight

kg/km

Cable

Weight

kg/km

4×6/6re

16.0

297.0

497

10×1.5/2.5re

16.9

172.0

415

4×10/10re

18.0

504.0

729

10×2.5/4re

18.5

282.0

552

4×16/16re

23.0

796.0

1149

4×25/16rm

27.0

1142.0

1616

12×1.5/2.5re

17.0

205.0

429

4×120/70rm

48.0

5388

5180

12×2.5/4re

19.0

334.0

600

4×150/70rm

53.0

6540

6501

12×4/6re

22.0

522.0

900.0

4×185/95rm

60.0

8159

7967

4×240/120rm

67.0

10546

12990

16×1.5/4re

20.0

270.0

684.0

4×35/16rm

30

1526.0

2059

16×2.5/6re

21.1

445.0

799.0

4×50/25rm

33.0

2203.0

2751

4×70/35rm

390

3082.0

3915

21×1.5/6re

22.0

362.0

761.0

4×95/50rm

44.0

4208.0

5180

21×2.5/6re

24.9

567.0

998.0

7×1.5/2.5re

14.0

133.0

284

24×1.5/6re

23.0

413.0

787.0

7×2.5/2.5re

15.0

200.0

377

24×2.5/10re

26.0

498.0

925.0

7×4/4 re

17.0

315.0

597

7×6/6 re

18.0

470.0

712

30×1.5/6re

25.0

499.0

920.0

30×2.5/10re

28.0

840.0

1317

N2XCH power cables, 0.6/1 kV, with concectric conductor, halogen free

For cross sections that are not mentioned on the table above, please contact our sales department.