Application
N2XH cable is used on indoor installations where special safety specifications are required for the human life protec-tion in case of fire. Mostly used into hospitals, underground stations, public places with big people concentration etc. Suitable for outdoor applications and underground installations into conduits or tubes.
Cable structure
Technical data
CoresSolid or stranded bare copper wires according to DIN VDE 0295 cl.1 or cl.2
Core insulationCross-linked polyethylene halogen free 2XI1 according to DIN VDE 0276-604
Color codingColor code according to DIN VDE 0293From 3 cores and above, it contains a green/yellowearthing coreCores are stranded in layers
WrappingHalogen free compound
Outer sheathThermoplastic polyolefin compound HM4 according to DIN VDE 0276-604, halogen free and flame retardant according to IEC 60332-3, black color
SpecificationsDIN VDE 0276-604
Temperature rangeFlexing from -5ºC up to +50ºCFixed installation from -30ºC up to +90ºC
Nominal voltageUo/U 0.6/1 kV
Minimum bending radiusSingle core 15 x cable ØMulticore 12 x cable Ø
re = round conductor, single wire
rm = round conductor, multi core
| power cables, 0.6/1 kV, halogen free
Approximately
Approximately
No. cores x
cross-sec
mm²
Outer
Diameter
Ø mm
Copper
Weight
kg/km
Cable
Weight
kg/km
No. cores x
cross-sec
mm²
Outer
Diameter
Ø mm
Copper
Weight
kg/km
Cable
Weight
kg/km
1×4 re
6.0
38.0
75
1×185 rm
23.0
1776.0
1888
1×6 re
7.0
58.0
97
1×240 rm
26.0
2304.0
2474
1×10 re
8.0
96.0
140
1×300 rm
28.0
2880.0
2946
1×16 re
9.0
154.0
202
1×25 rm
11.0
240.0
302
2×1.5 re
11.5
29.0
187
1×35 rm
12.0
336.0
397
2×2.5 re
11.7
48.0
218
1×50 rm
13.0
480.0
523
2×4 re
13.0
77.0
270
1×70 rm
15.0
672.0
746
2×6 re
13.9
115.0
341
1×95 rm
17.0
912.0
987
2×10 re
16.2
192.0
445
1×120 rm
18.0
1152.0
1214
2×16 re
17.8
307.0
617
1×150 rm
21.0
1440.0
1536
2×25 re
21.0
480.0
935
N2XH 0.6/1kV CE
N2XH
www.vopcables.com
Power Cables
Approximately
Approximately
No. cores x
cross-sec
mm²
Outer
Diameter
Ø mm
Copper
Weight
kg/km
Cable
Weight
kg/km
No. cores x
cross-sec
mm²
Outer
Diameter
Ø mm
Copper
Weight
kg/km
Cable
Weight
kg/km
3G1.5 re
13.0
43.0
220
4G185 rm
52.0
7104.0
8160
3G2.5 re
14.0
72.0
280
4G240 rm
58.0
9216.0
10540
3G4 re
15.0
115.0
350
3G6 re
16.0
173.0
420
5G1.5 re
13.0
72.0
280
3G10 re
18.0
288.0
600
5G2.5 re
14.0
120.0
350
3G16 re
20.0
461.0
770
5G4 re
15.0
192.0
450
3G25 rm
21.8
720.0
1120
5G6 re
16.0
288.0
600
3G35 rm
24.9
1008.0
1550
5G10 re
19.0
480.0
850
3G50/25 rm
28.5
1680.0
2100
5G16 rm
23.0
768.0
1200
3G50 rm
25.2
1440.0
1750
5G25 rm
27.0
1200.0
1702
3G70 rm
29.2
2016.0
2450
3G70/35 rm
31.4
2352.0
2800
7G1.5 re
14.0
101.0
260
3G95 rm
32.0
2736.0
3250
7G2.5 re
16.0
168.0
358
3G95/50 rm
34.9
3216.0
3750
7G4 re
17.2
269.0
530
3G120 rm
34.9
3456.0
4000
3G120/70 rm
38.0
4128.0
4750
10G1.5 re
17.0
144.0
268
3G150 rm
39.2
4320.0
5000
10G2.5 re
19.0
240.0
484
3G150/70 rm
43.3
4992.0
5750
3G185 rm
44.1
5328.0
6150
12G1.5 re
17.0
173.0
410
3G185/95 rm
47.2
6240.0
7200
12G2.5 re
19.0
288.0
542
3G240/120rm
53.4
8064.0
9300
12G4 re
21.2
461.0
786
3G240 rm
49.2
6912.0
8000
14G1.5 re
18.0
202.0
448
4G1.5 re
12.0
58.0
186
14G2.5 re
22.0
336.0
630
4G2.5 re
13.0
96.0
245
4G4 re
14.0
154.0
328
19G1.5 re
19.0
274.0
558
4G6 re
15.0
230.0
425
19G2.5 re
24.0
456.0
800
4G10 re
17.0
384.0
625
4G16 re
20.0
614.0
921
24G1.5 re
23.0
346.0
743
4G25 rm
24.0
960.0
1403
24G2.5 re
27.0
576.0
990
4G35 rm
27.0
1344.0
1860
4G50 rm
31.0
1920.0
2470
30G1.5 re
24.0
432.0
853
4G70 rm
36.0
2668.0
3510
30G2.5 re
28.0
720.0
1180
4G95 rm
41.0
3648.0
4695
4G120 rm
43.0
4608.0
5380
33G2.5 re
29.0
792.0
1302
4G150 rm
47.0
5760.0
6590
N2XH power cables 0.6/1 kV, halogen free
For cross sections that are not mentioned on the table above, please contact our sales department.
www.vopcables.com
Power Cables