VOP Cables

Vop_Catalogue_2020_WEB_USE_ONLY_ENG-156

Application

This cable is used on fixed installations mostly for outdoor power supply stations. Suitable to be used on cable trays, switch-boards and power stations. It can be laid easily in difficult line guides. Outer sheath of PE offers special resistance to mechanical stress. The inner conducting layer between the conductor and the XLPE and the firmly bonded outer conducting layer on the XLPE, assures a construction free of partial discharges with high operational reliability.

Cable structure

Technical data

CoresCircular bare copper conductor of stranded wiresaccording to DIN DIN VDE 0295 cl.2

Core insulation1st insulationInner semi-conducting coating

2nd insulationCross-linked compound (XLPE) DIX8 according to HD 620 S2

3rd insulationOuter semi-conducting coating spliced with the XLPE insulation

WrappingConductive material

Screening Copper wire braiding with one or two tapes applied helically

Outer sheathPE type HD 620 S2, black color

SpecificationsDIN VDE 0276, HD 620 S2 και IEC 60502

Temperature rangeDuring the installation up to -20ºCFixed installation up to +90ºCShort circuit temperature up to +250ºC (up to 5 sec)

Nominal voltageUo/U 6/10 kV maximum 12 kVUo/U 12/20 kV maximum 24 kVUo/U 12/30 kV maximum 36 kV

Minimum bending radius15 x Ø cable

| aluminium medium voltage cables with| outer sheath of polyethylene

NA2XS2Y

Cores x cross-secin mm²

Nominalvoltage

Approximately

Outer Diameter

Ø mmMin Max

Copper Weight

kg/km

Aluminium Weight

kg/km

Cable Weight

kg/km

1x50rm/16

6/10

24.0-29.0

182.0

145.0

710.0

1x70rm/16

6/10

26.0-31.0

182.0

203.0

790.0

1x95rm/16

6/10

26.0-32.0

182.0

276.0

920.0

1x120rm/16

6/10

28.0-34.0

182.0

348.0

990.0

1x150rm/16

6/10

29.0-35.0

182.0

435.0

1110.0

1x150rm/25

6/10

30.0-35.0

283.0

435.0

1220.0

1x185rm/16

6/10

31.0-37.0

182.0

537.0

1260.0

1x185rm/25

6/10

31.0-37.0

283.0

537.0

1370.0

www.vopcables.com

Medium Voltage Cables

Vop_Catalogue_2020_WEB_USE_ONLY_ENG-157

NA2XS2Y aluminium medium voltage cables with outer sheath of polyethylene6/10 kV, 12/20 kV, 20/30 kV

Cores x cross-secin mm²

Nominalvoltage

Approximately

Outer Diameter

Ø mmMin Max

Copper Weight

kg/km

Aluminium Weight

kg/km

Cable Weight

kg/km

1x240rm/16

6/10

33.0-39.0

182.0

696.0

1480.0

1x240rm/25

6/10

33.0-39.0

283.0

696.0

1530.0

1x300rm/25

6/10

36.0-41.0

283.0

870.0

1820.0

1x400rm/35

6/10

40.0-45.0

394.0

1160.0

2220.0

1x500rm/35

6/10

43.0-48.0

394.0

1450.0

2570.0

1x50rm/16

12/20

28.0-33.0

182.0

145.0

890.0

1x70rm/16

12/20

30.0-35.0

182.0

203.0

970.0

1x95rm/16

12/20

31.0-36.0

182.0

276.0

1120.0

1x120rm/16

12/20

33.0-38.0

182.0

348.0

1210.0

1x150rm/16

12/20

34.0-39.0

182.0

435.0

1370.0

1x150rm/25

12/20

34.0-39.0

283.0

435.0

1420.0

1x185rm/16

12/20

36.0-41.0

182.0

537.0

1530.0

1x185rm/25

12/20

36.0-41.0

283.0

537.0

1570.0

1x240rm/16

12/20

39.0-44.0

182.0

696.0

1720.0

1x240rm/25

12/20

39.0-44.0

283.0

696.0

1830.0

1x300rm/25

12/20

41.0-46.0

283.0

870.0

2070.0

1x400rm/35

12/20

44.0-49.0

394.0

1160.0

2460.0

1x500rm/35

12/20

46.0-52.0

394.0

1450.0

2890.0

1x600rm/35

12/20

47.0-53.0

394.0

1827.0

3370.0

1x50rm/16

18/30

32.0-38.0

182.0

145.0

1120.0

1x70rm/16

18/30

34.0-40.0

182.0

203.0

1270.0

1x95rm/16

18/30

35.0-41.0

182.0

276.0

1380.0

1x120rm/16

18/30

37.0-43.0

182.0

348.0

1530.0

1x150rm/25

18/30

38.0-44.0

283.0

435.0

1720.0

1x185rm/25

18/30

40.0-46.0

283.0

537.0

1860.0

1x240rm/25

18/30

42.0-48.0

283.0

696.0

2110.0

1x300rm/25

18/30

45.0-51.0

283.0

870.0

2370.0

1x400rm/35

18/30

48.0-54.0

394.0

1160.0

2820.0

1x500rm/35

18/30

51.0-57.0

394.0

1450.0

3280.0

1x600rm/35

18/30

52.0-59.0

394.0

1827.0

3770.0

This cable is also available in types NΑ2XS(F)2Y and NΑ2XS(FL)2Y in 6/10 kV, 12/20 kV, 18/30 kV.

www.vopcables.com

Medium Voltage Cables