VOP Cables

Application

This cable is used in both outdoor installations and in cable ducts, outdoors, underground or in the water due to the longitudinally watertight conductive wrapping that exists over the conductive layer which is welded with the core insulation. Suitable to be used on cable trays, switch-boards and power stations. It can easily be laid in difficult line guides. Outer sheath of PE offers special resistance to mechanical stress. The inner conducting layer between the conductor and the XLPE and the firmly bonded outer conducting layer on the XLPE, assures a construction free of partial discharges with the operational reliability.

Cable structure

Technical data

CoresCircular bare copper conductor of stranded wires according to DIN VDE 0295 cl.2 and IEC 60228 cl.2

Core insulation1st insulationInner semi-conducting coating

2nd insulationCross-linked compound (XLPE) DIX8 according to HD 620 S2

3rd insulationOuter semi-conducting coating spliced with the XLPE insulation

WrappingLongitudinally watertight, conductive wrapping

Screening Copper wire braiding with one or two tapes applied helically

Outer sheathPE type HD 620 S2, black color

SpecificationsDIN VDE 0276 part 620, HD 620 S2 and IEC 60502

Temperature rangeDuring installation up to -20ºC

Fixed installation up to +90ºC

Short circuit temperature up to +250ºC (up to 5 sec)

Nominal voltageUo/U 6/10 kV max 12 kV

Uo/U 12/20 kV max 24 kV

Uo/U 12/30 kV max 36 kV

Minimum bending radius15 x Ø cable

Cores x cross-secin mm²

Nominalvoltage

Approximately

Outer Diameter

Ø mmMin Max

Copper Weight

kg/km

Aluminium Weight

kg/km

Cable Weight

kg/km

1x35rm/16

6/10

26

182

102

780

1x50rm/16

6/10

28

182

145

850

1x70rm/16

6/10

30

182

203

980

1x95rm/16

6/10

31

182

276

1080

1x120rm/16

6/10

32

182

348

1150

1x150rm/25

6/10

34

283

435

1280

1x185rm/25

6/10

36

283

537

1420

1x240rm/25

6/10

38

283

696

1630

| aluminium medium voltage cables with outer | sheath of polyethylene, longitudinally watertight

| 6/10 kV, 12/20 kV, 18/30 kV

NA2XS(F)2Y

www.vopcables.com

Medium Voltage Cables

NA2XS(F)2Y aluminium medium voltage cables with outer sheath of polyethylene,

longitudinally watertight 6/10 kV, 12/20 kV, 18/30 kV

Cores x cross-secin mm²

Nominalvoltage

Approximately

Outer Diameter

Ø mmMin Max

Copper Weight

kg/km

Aluminium Weight

kg/km

Cable Weight

kg/km

1x300rm/25

6/10

40

283

870

1950

1x400rm/35

6/10

44

394

1160

2350

1x500rm/35

6/10

47

394

1450

2780

1x50rm/16

12/20

33

182

145

920

1x70rm/16

12/20

34

182

203

1030

1x95rm/16

12/20

36

182

276

1140

1x120rm/16

12/20

37

182

348

1250

1x150rm/25

12/20

39

283

435

1320

1x185rm/25

12/20

41

283

537

1570

1x240rm/25

12/20

42

182

696

1679

1x240rm/25

12/20

43

283

696

1780

1x300rm/25

12/20

45

283

870

2100

1x400rm/35

12/20

48

394

1160

2480

1x500rm/35

12/20

50

394

1450

2900

1x630rm/35

12/20

52

394

1827

3380

1x800rm/35

12/20

57

394

2320

4400

1x1000rm/35

12/20

62

394

2900

4780

1x50rm/16

12/20

37

182

145

1250

1x70rm/16

18/30

38

182

203

1500

1x95rm/16

18/30

40

182

276

1700

1x120rm/16

18/30

42

182

348

1800

1x150rm/25

18/30

43

283

435

2050

1x185rm/25

18/30

45

283

537

2150

1x240rm/25

18/30

47

283

696

2400

1x300rm/25

18/30

50

283

870

2700

1x400rm/35

18/30

53

394

1160

3200

1x500rm/35

18/30

56

394

1450

3555

1x630rm/35

18/30

58

394

1827

3790