Application
This cable is suitable for all types of underground and open air solar installations. It is recommended for connections between photovoltaic parts.
Cable structure
Technical data
Cores
Circular compacted stranded aluminium conductor according to IEC 60228 cl.2
Core insulation
Cross-linked compound (XLPE) according to IEC 60502-1
Outer sheath
PVC UV resistant, black color
Specifications
IEC 60502-1
Temperature range
Maximum permissible conductor temperature up to +90ºC
Short circuit temperature up to +250ºC (up to 5 sec)
Nominal voltage
Uo/U 900/1500 (1800)V DC
Conductor resistance
0.125 Ω/km (at +20ºC)
0.160 Ω/km (at +90ºC)
Minimum bending radius
5 x Ø cable (fixed installation)
| power cables 1500V
NA2XY
www.vopcables.com
Power Cables
Cores x cross-sec
in mm²
Approximately
Outer
Diameter
Ø mm
Aluminium
Weight
kg/km
Cable
Weight
kg/km
1×35
11.5
89
183
1×50
13
122
232
1×70
14.8
173
305
1×95
16.7
236
400
1×120
18.4
304
485
1×150
20.4
376
595
1×185
23.3
470
740
1×240
25.5
590
910
1×300
28.5
738
1115
1×400
32.3
990
1440