Application
This type is used on indoor installations, wherever high security specifications are required for the protection from fire of human life. When burnt this cable, the circuit integrity is maintained for 30 minutes, while there appear low smoke and halogen emissions. Not recommended for direct burial underground or underwater without conduits or tubes.

Cable structure
Technical data
CoresSolid or stranded bare copper wires according toDIN VDE 0295 cl.1 and IEC 60228 cl.1 and cl.2
Core insulation1st insulationHigh quality flame resistant, ceramic compound2nd insulationCross-linked polymer compoundHxI1 according to DIN VDE 0266
Color codingAccording to DIN VDE 0293, from 3 cores and abovecontains green/yellow earthing core
WrappingHalogen free compound
ScreeningConcetric conductor of copper wires wrappedwith copper tape
SeparatorPlastic tape
Outer sheathPolyolefin compound HM4accordiong to DIN VDE 0276-604,CENELEC HD 604S1, in orange color
re = round conductor, single wire
rm = round conductor, multiple wire
SpecificationsDIN VDE 0276-604
Temperature rangeDuring installation: from -5°C up to +50°C
Fixed installation: from -5°C up to +90°C
Nominal voltageUo/U 0.6/1 kV
Minimum bending radius12 x cable Ø
Halogen freeDIN VDE 0482-267, EN 50267 and IEC 60754-2
Flame retardantDIN VDE 0482-265, EN 50265 and IEC 60332-1
Reduced flame propagationDIN VDE 0472-804/C, CENELEC HD 405.3 and IEC 60332-3 cat C and cat A
Low smoke emissionDIN VDE 0482-268, EN 50268 and IEC 61034-
Insulation integrity FE180DIN VDE 0472-814, IEC 60331, NBN C30-004 cat.F3
Funcionality E30DIN 41012-12
NHXCH FE180/E30
Approximately
Approximately
No. cores x
cross-sec
mm²
Outer
Diameter
Ø mm
Copper
Weight
kg/km
Cable
Weight
kg/km
No. cores x
cross-sec
mm²
Outer
Diameter
Ø mm
Copper
Weight
kg/km
Cable
Weight
kg/km
2×1.5 re/1.5
14.0
52.0
272
3×1.5 re/1.5
15.0
66.0
302
2×2.5 re/2.5
15.0
80.0
325
3×2.5 re/2.5
16.0
104.0
365
2×4 re/4
16.0
123.0
411
3×4 re/4
17.0
161.0
467
2×6 re/6
17.0
182.0
496
3×6 re /6
18.0
240.0
571
2×10 re/10
19.0
312.0
670
3×10 re/10
20.0
408.0
783
NHXCH FE180/E30 0.6/1KV
| fire resistant power and control cables 0.6/1 kV, with
| concetric conductor, for circuit integrity 30 minutes
Fire Resistant Cables
www.vopcables.com

Approximately
Approximately
No. cores x
cross-sec
mm²
Outer
Diameter
Ø mm
Copper
Weight
kg/km
Cable
Weight
kg/km
No. cores x
cross-sec
mm²
Outer
Diameter
Ø mm
Copper
Weight
kg/km
Cable
Weight
kg/km
3×16 rm/16
24.0
643.0
1148
4×10 re/10
22.0
504.0
944
3×35 rm/16
30.0
1003.0
1552
4×16 rm/16
26.0
796.0
1390
3×25 rm/16
27.0
1402.0
1941
4×25 rm/16
30.0
1142.0
1403
3×50 rm/25
33.0
1723.0
2554
4×35 rm/16
33.0
1526.0
2383
3×70 rm/35
38.0
2410.0
3484
4×50 rm/25
37.0
2203.0
3179
3×95 rm/50
44.0
3296.0
4678
4×70 rm/35
42.0
3082.0
4349
3×120 rm/70
46.0
4236.0
5700
4×95 rm/50
48.0
4208.0
4838
3×150 rm/70
51.0
5100.0
6921
4×120 rm/70
51.0
5388.0
7099
3×185 rm/95
57.0
6383.0
8639
4×150 rm/70
57.0
6540.0
8690
3×240 rm/120
65.0
8242.0
11253
4×185 rm/95
64.0
8159.0
10824
4×240 rm/120
72.0
10546.0
14134
4×1.5 re /1.5
16.0
81.0
349
4×2.5 re/2.5
17.0
128.0
428
7×1.5 re/2.5
18.0
133.0
492
4×4 re /4
19.0
200.0
548
4×6 re/6
20.0
297.0
676
30×1.5re/6
34.0
499.0
1564
For cross sections that are not mentioned on the above table, please contact our sales department.
NHXCH FE180/E30 fire resistant power and control cables 0.6/1 kV, with concetricconductor, for circuit integrity 30 minutes
www.vopcables.com