VOP Cables

Vop_Catalogue_2020_WEB_USE_ONLY_ENG-167

Application

This type is used on indoor installations, wherever high security specifications are required for the protection from fire of human life. When burnt this cable, the circuit integrity is maintained for 30 minutes, while there appear low smoke and halogen emissions. Not recommended for direct burial underground or underwater without conduits or tubes.

Cable structure

Technical data

CoresSolid or stranded bare copper wires according toDIN VDE 0295 cl.1 and cl.2

Core insulation1st insulationHigh quality flame resistant, ceramic compound2nd insulationCross-linked polymer compoundHxI1 according to DIN VDE 0266

Color codingAccording to DIN VDE 0293, from 3 cores and abovecontains green/yellow earthing core

WrappingHalogen free compound

ScreeningConcetric conductor of copper wires wrappedwith copper tape

SeparatorPlastic tape

Outer sheathPolyolefin compound HM4accordiong to DIN VDE 0276-604,CENELEC HD 604S1, in orange color

re = round conductor, single wire

rm = round conductor, multiple wire

SpecificationsDIN VDE 0276-604

Temperature rangeFrom –5ºC up to +90ºC

Nominal voltageUo/U 0.6/1 kV

Minimum bending radius15 x cable Ø

Halogen freeDIN VDE 0482-267, EN 50267 and IEC 60754-2

Flame retardantDIN VDE 0482-265, EN 50265 and IEC 60332-1

Reduced flame propagationDIN VDE 0472-804/C, CENELEC HD 405.3 and IEC 60332-3 cat C and cat A

Low smoke emissionDIN VDE 0482-268, EN 50268 and IEC 61034-

Insulation integrity FE180DIN VDE 0472-814, IEC 60331, NBN C30-004 cat.F3

Funcionality E30DIN 41012-12

NHXCH FE180/E30

Approximately

Approximately

No. cores x

cross-sec

mm²

Outer

Diameter

Ø mm

Copper

Weight

kg/km

Cable

Weight

kg/km

No. cores x

cross-sec

mm²

Outer

Diameter

Ø mm

Copper

Weight

kg/km

Cable

Weight

kg/km

2×1.5 re/1.5

14.0

52.0

272

3×1.5 re/1.5

15.0

66.0

302

2×2.5 re/2.5

15.0

80.0

325

3×2.5 re/2.5

16.0

104.0

365

2×4 re/4

16.0

123.0

411

3×4 re/4

17.0

161.0

467

2×6 re/6

17.0

182.0

496

3×6 re /6

18.0

240.0

571

2×10 re/10

19.0

312.0

670

3×10 re/10

20.0

408.0

783

NHXCH FE180/E30 0.6/1KV

| fire resistant power and control cables 0.6/1 kV, with

| concetric conductor, for circuit integrity 30 minutes

www.vopcables.com

Fire Resistant Cables

Vop_Catalogue_2020_WEB_USE_ONLY_ENG-168

NHXCH FE180/E30 πυράντοχα καλώδια ισχύος και ελέγχου 0.6/1 kV, με ομοκεντρικό αγωγό, για διατήρηση κυκλώματος 30 λεπτά

Approximately

Approximately

No. cores x

cross-sec

mm²

Outer

Diameter

Ø mm

Copper

Weight

kg/km

Cable

Weight

kg/km

No. cores x

cross-sec

mm²

Outer

Diameter

Ø mm

Copper

Weight

kg/km

Cable

Weight

kg/km

3×16 rm/16

24.0

643.0

1148

4×10 re/10

22.0

504.0

944

3×35 rm/16

30.0

1003.0

1552

4×16 rm/16

26.0

796.0

1390

3×25 rm/16

27.0

1402.0

1941

4×25 rm/16

30.0

1142.0

1403

3×50 rm/25

33.0

1723.0

2554

4×35 rm/16

33.0

1526.0

2383

3×70 rm/35

38.0

2410.0

3484

4×50 rm/25

37.0

2203.0

3179

3×95 rm/50

44.0

3296.0

4678

4×70 rm/35

42.0

3082.0

4349

3×120 rm/70

46.0

4236.0

5700

4×95 rm/50

48.0

4208.0

4838

3×150 rm/70

51.0

5100.0

6921

4×120 rm/70

51.0

5388.0

7099

3×185 rm/95

57.0

6383.0

8639

4×150 rm/70

57.0

6540.0

8690

3×240 rm/120

65.0

8242.0

11253

4×185 rm/95

64.0

8159.0

10824

4×240 rm/120

72.0

10546.0

14134

4×1.5 re /1.5

16.0

81.0

349

4×2.5 re/2.5

17.0

128.0

428

7×1.5 re/2.5

18.0

133.0

492

4×4 re /4

19.0

200.0

548

4×6 re/6

20.0

297.0

676

30×1.5re/6

34.0

499.0

1564

For cross sections that are not mentioned on the above table, please contact our sales department.

NHXCH FE180/E30 fire resistant power and control cables 0.6/1 kV, with concetricconductor, for circuit integrity 30 minutes

www.vopcables.com

Fire Resistant Cables