VOP Cables

Vop_Catalogue_2020_WEB_USE_ONLY_ENG-133

| low smoke and halogen free cables, flame retardant| according to IEC 0332-3 CAT.C

NHXMH J 3G6 mm²

NHXMH

Application

These cables are used on indoor installations where special safety specifications are required for the human life protection in case of fire. Mostly used into hospitals, underground stations, public places with big people concentration etc. They are not suitable for direct embedding.

Cable structure

Technical data

CoresSolid or stranded bare copper wires according to DIN VDE 0295 cl.1 or cl.2 and IEC 60228 cl.1 or cl.2

Core insulationCross-linked polymer compound 2xI1 according to DIN VDE 0276-604

Color codingUp to 5 cores, color coding according to DIN VDE 0293, from 7 cores and above, black cores with white numberingThe single core cables comes in black color

WrappingΗalogen free sheath (not for single core cables)

Outer sheathPolymer compound HM2, halogen free according to DIN VDE 0250-214 and flame retardant according toDIN VDE 0482-265, in grey color

StandardsDIN VDE 0250 part 214

Temperature rangeFlexing from -5ºC up tp +50ºCFixed installation from -30ºC up to +70ºC

Nominal voltageUo/U 300/500 V

Minimum bending radiusSingle core 15 x cable ØMulti cores 12 x cable Ø

re = round solid core

rm = round multi core

Approximately

Approximately

No. cores x

cross-sec

mm²

Outer

Diameter

Ø mm

Copper

Weight

kg/km

Cable

Weight

kg/km

No. cores x

cross-sec

mm²

Outer

Diameter

Ø mm

Copper

Weight

kg/km

Cable

Weight

kg/km

1×1.5 re

8.0

15.0

49

3×1.5 re

9.7

43.0

130

1×2.5 re

8.5

24.0

60

3×2.5 re

10.8

72.0

167

1×4 re

9.0

39.0

80

3×4 re

12.0

115.0

235

1×6 re

10.4

58.0

111

3×6 re

13.8

173.0

325

1×10 re

11.9

96.0

160

3×10 re

16.6

288.0

482

1×16 rm

12.6

154.0

232

3×16 rm

20.0

461.0

846

3×25 rm

25.0

720.0

1140

2×1.5 re

9.3

29.0

120

3×35 rm

27.5

1008.0

1500

2×2.5 re

10.4

48.0

154

2×4 re

11.5

77.0

202

4×1.5 re

10.6

58.0

150

4×2.5 re

11.7

96.0

201

www.vopcables.com

Power Cables

Vop_Catalogue_2020_WEB_USE_ONLY_ENG-134

NHXMH καλώδια ελεύθερα καπνού και αλογόνων, βραδύκαυστα κατά IEC 60332-3 CAT. C

Approximately

Approximately

No. cores x

cross-sec

mm²

Outer

Diameter

Ø mm

Copper

Weight

kg/km

Cable

Weight

kg/km

No. cores x

cross-sec

mm²

Outer

Diameter

Ø mm

Copper

Weight

kg/km

Cable

Weight

kg/km

4×4 re

13.8

154.0

300

5×16 rm

24.5

768.0

1143

4×6 re

15.2

230.0

396

5×25 rm

29.6

1200.0

1790

4×10 re

17.9

384.0

598

5×35 rm

33.1

1680.0

2468

4×16 re

22.1

615.0

938

4×25 rm

27.5

960.0

1425

7×1.5 re

11.9

101.0

212

4×35 rm

30.4

1344.0

1920

7×2.5 re

14.0

168.0

300

5×1.5 re

11.2

72.0

176

10×1.5 re

14.0

144.0

325

5×2.5 re

12.1

120.0

235

5×4 re

15.3

192.0

351

12×1.5 re

15.0

173.0

361

5×6 re

16.3

288.0

481

5×10 re

19.4

480.0

715

24×1.5 re

19.0

346.0

627

Low smoke and halogen free cables, flame retardant according to IEC 0332-3 CAT.C

For cross sections that are not mentioned, please contact our sales department.

www.vopcables.com

Power Cables

Contact

    This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.